FDUM140AVSXVF, 14.0kW

Key features

  • Single Phase model
  • Automatic External Static Pressure control
  • Weekly / Sleep timer
  • Self-diagnostics function
  • 600mm built-in drain pump
Set   FDUM140AVSXVF
Indoor   FDUM140VF
Outdoor   FDCA140VSX
Power supply Outdoor Unit   3 Phase 415V 50Hz
CapacityØ Cooling T1 kW 14.0 (5.0-14.5)
Heating H1 16.0 (4.0-16.5)
Heating H2 NA
InputØ Cooling T1 kW 4.40
Heating H1 4.54
Max running current   A 15
EER Cooling T1   3.18
COP Heating H1   3.52
Sound pressure level (JIS C9612)Ø Indoor dB (A) P-Hi:47 Hi:40 Me:35 Lo:30
Outdoor 49
Sound power level (JIS C9612) Outdoor dB(A) 70
Airflow Indoor l/s P-Hi:800 Hi:583 Me:467 Lo:367
External Static Pressure   Pa 100@800 l/s
External dimensions (HXWXD) Indoor mm 280x1370x740
Outdoor 1300x970x370
Net weight Indoor kg 54
Outdoor 105
Refrigerant piping Liquid line mm Ø9.52
Gas line Ø15.88
Connection method   Flare Connection
Refrigerant R410A Quantity kg 4.5
Pre charged to pipe length m 30
Maximum pipe length m 100
Supply air connection mm 170 x 1200
Return air connection mm 235 x 1280
Controller   RC-E5, RC-EX3 or RCN-KIT4-E2